Air handling & heating
Engineered Air LM10/C air handling unit, 9,625 CFM, new
CA$21,000 each
7 available
RVF-201

1 / 1
Air handling & heating
RVF-202
A new, unused Engineered Air LM13/C indoor air handling unit rated 11,000 CFM on 575 V three-phase power. Six are available. It is a hydronic unit with a hot-water heating coil and a chilled-water cooling coil, so there is no compressor to service. A fit for a Canadian building or process on a central water plant.
Asking price
CA$26,500 each
6 available Canadian dollars, plus applicable taxes. Offers are welcome.
Sold as is, where is. Inspection by appointment. Freight quoted per lot, buyer's account. Terms of sale.
The LM13/C is a Canadian-built indoor air handler from Engineered Air. Each unit has a belt-drive supply fan, a hot-water heating coil and a chilled-water cooling coil in one casing. Heating and cooling come from the building's boiler and chiller; the unit moves and conditions the air.
The nameplate describes it as a heating unit with cooling for indoor installation. It reads 11,000 CFM at 1 in. w.c. external static pressure, with a 15 HP supply fan motor on 575 V, 3 phase, 60 Hz.
The consulting engineer's design schedule for this unit puts the duty at 341 MBH heating and 616 to 660 MBH cooling. That is a design figure, not a factory rating: coil capacity depends on your water temperature and flow.
| Item | Qty | Make | Model |
|---|---|---|---|
| Engineered Air LM13/C (11,000 CFM) · Supplemental flower-room AHU, DBM-007 R8.0 allocation to room 301 | 1 | Engineered Air | LM13/C (11,000 CFM) |
| Engineered Air LM13/C (11,000 CFM) · Supplemental flower-room AHU, DBM-007 R8.0 allocation to room 302 | 1 | Engineered Air | LM13/C (11,000 CFM) |
| Engineered Air LM13/C (11,000 CFM) · Supplemental flower-room AHU, DBM-007 R8.0 allocation to room 303 | 1 | Engineered Air | LM13/C (11,000 CFM) |
| Engineered Air LM13/C (11,000 CFM) · Supplemental flower-room AHU, DBM-007 R8.0 allocation to room 304 | 1 | Engineered Air | LM13/C (11,000 CFM) |
| Engineered Air LM13/C (11,000 CFM) · Supplemental flower-room AHU, DBM-007 R8.0 allocation to room 305 | 1 | Engineered Air | LM13/C (11,000 CFM) |
| Engineered Air LM13/C (11,000 CFM) · Supplemental flower-room AHU, DBM-007 R8.0 allocation to room 306 | 1 | Engineered Air | LM13/C (11,000 CFM) |
| Maker | Engineered Air |
|---|---|
| Model | LM13/C |
| Quantity | 6 |
| Type | Indoor hydronic air handling unit: hot-water heating, chilled-water cooling (no compressor, not DX) |
| Supply airflow | 11,000 CFM at 1 in. w.c. external static pressure (nameplate) |
| Electrical | 575 V, 3 phase, 60 Hz |
| Supply fan | Size 22, belt drive, 1,620 rpm; belts (2) B-76 |
| Supply fan motor | 15 HP, 14.6 FLA, 92.4 % efficiency |
| Heating coil | Hot water; 32 °F temperature rise; 150 psig max working pressure; 230 °F max inlet water or glycol |
| Cooling coil | Chilled water; 150 psig max working pressure |
| Design duty | 341 MBH heating; 616 to 660 MBH cooling (design schedule, not a factory rating) |
| Filters | 8 pleated pre-filters and 8 final filters, 20 × 20 × 2 in. (design schedule) |
| Size | 188 × 88 × 53 in., L × W × H (design schedule) |
| Weight | 4,600 lb (design schedule) |
| Clearance to combustibles | 1 in. front, top and side; 0 in. bottom and back; service side one unit width |
| Certification | CSA C22.2 No. 236-2011; cETL listed (Intertek) |
| Nameplate date | October 2018 (the plate photographed) |
New, unused. Rig Out has read the nameplate on one unit of this model, shown in the photo; the plates on the other units and the coils have not been inspected one by one, and the units have not been run. Serial numbers and nameplate photos for each unit are available on request. Sold as is, where is. Inspection is welcome by appointment in the Edmonton area, Alberta, Canada.
Rig Out loads each unit and can crate or skid them for the road. They can be export packed, and on request we quote FOB Port of Vancouver or to Edmonton rail. Freight is quoted per order and is to the buyer's account.