Rig OutAsk a question
Bank of Multistack modular chiller modules as installed in the plant room

1 / 5

Chiller plant

Multistack heat-recovery chiller plant with Marley cooling tower

RVF-307

A complete central thermal plant sold as one package: five Multistack water-cooled chiller modules scheduled at 680 tons nominal, a Multistack dedicated heat-recovery chiller, a Marley cooling tower and sixteen Armstrong pumps, with buffer tanks, make-up air and controls. The chiller plant was selected and installed to one design schedule and saw about nine months in service. It is drained, skidded and shrink-wrapped. The Armstrong gas boilers are listed separately.

Asking price

CA$817,500

Canadian dollars, plus applicable taxes. Offers are welcome.

Sold as is, where is. Inspection by appointment. Freight quoted per lot, buyer's account. Terms of sale.

Overview

This is the heating and cooling plant for a large building, offered whole. Five Multistack MS145 modular chiller modules make chilled glycol and reject their heat to a Marley induced-draft crossflow cooling tower. A sixth Multistack machine, an MSH165 dedicated heat-recovery chiller, captures heat from the cooling side and returns it to the heating loop. The Armstrong gas boilers that carried the rest of the heating load are listed separately and are not part of this lot.

Sixteen Armstrong pumps move the loops, with N+1 pumping on the chilled-glycol, condenser-water and boiler loops. Two Taco buffer tanks steady the chilled and heating loops. A gas-fired Engineered Air make-up air unit, two Greenheck roof exhaust fans and an Allen-Bradley distributed I/O block complete the package.

Modular chillers suit a staged project: the modules are separate cabinets that move through a standard doorway, and capacity is built up module by module. Because every major item here was chosen to one schedule, a buyer takes on a matched plant instead of assembling one from mixed sources. Capacities quoted are design-schedule and nameplate values, not a field test. The equipment schedule and nameplate readings are available on request.

What's included

  • 5 × Multistack MS145XC2C1W2AA-410A modular water-cooled chiller modules, R-410A
  • 1 × Multistack MSH165XCCMEAA-BHMHM-AAQ-DC-B-R410A dedicated heat-recovery chiller, R-410A
  • 1 × Marley AV6805QAN3 cooling tower, two fan branches
  • 1 × ZeeBest ST-1550 cooling tower tank
  • 3 × Armstrong 4300 6×6×10 chiller pumps
  • 3 × Armstrong 4300 5×5×11½ chiller glycol pumps
  • 3 × Armstrong 4300 6×6×11½ condenser-water pumps
  • 2 × Armstrong 4380 heat-recovery pumps, one glycol side and one hot-water side
  • 2 × Armstrong 4300 2×2×6 heating pumps
  • 2 × Armstrong 4380 2×2×6 boiler pumps
  • 1 × Armstrong Astro 225 BS domestic hot-water circulator
  • 1 × Taco BT3000F 125N chiller buffer tank
  • 1 × Taco BT2000F 125N heating buffer tank
  • 1 × Watts DETA 12 domestic hot-water expansion tank
  • 1 × Engineered Air FWX73/DJS40/O gas-fired make-up air unit
  • 2 × Greenheck USF-12 roof exhaust fans, interlocked with the make-up air unit
  • 1 × Allen-Bradley 1738 distributed I/O block (plant controls)
Full item register (20 lines)
Items in this package
ItemQtyMakeModel
40 ft. seacan container1
Dedicated heat-recovery chiller (nameplate model; the list carried 1MS165XC2C1H2AAC-410A)1MultistackMSH165XCCMEAA-BHMHM-AAQ-DC-B-R410A
Modular water-cooled chiller module5MultistackMS145XC2C1W2AA-410A
Cooling tower platform (two fan branches CT-1A and CT-1B)1MarleyAV6805QAN3
Cooling tower tank1ZeeBestST-1550
Chiller glycol pump3Armstrong4300 5×5×11½
Chiller pump3Armstrong4300 6×6×10
Heat-recovery pump, glycol side (2020 schedule; the list carried 'condensate heat-recovery pump')1Armstrong4380 0.08-005
Heat-recovery pump, hot-water side1Armstrong4380 0.08-005
Chiller buffer tank1TacoBT3000F 125N
Heating buffer tank1TacoBT2000F 125N
Heating pump2Armstrong4300 2×2×6
Boiler pump2Armstrong4380 2×2×6
DHW expansion tank1WattsDETA 12
DHWT circulator1ArmstrongAstro 225 BS
Engineered Air FWX73/DJS40/O make-up air unit; gas-fired 91 MBH heat, 3000 CFM, 1" ESP, MERV8 pre + MERV15 final filtration. (Acacia M3.0)1Engineered AirFWX73/DJS40/O
Greenheck USF-12 roof exhaust fan; 1500 CFM, 2.0" ESP. Interlocked with MUA-1. (Acacia M3.0)1GreenheckUSF-12
Greenheck USF-12 roof exhaust fan; 1700 CFM, 2.5" ESP. Interlocked with MUA-1. (Acacia M3.0)1GreenheckUSF-12
Condensate pump3Armstrong4300 6×6×11½
Distributed I/O1Allen-Bradley1738 I/O

Specifications

PackageComplete central thermal plant, sold as one lot
MakersMultistack, Marley, Armstrong, Taco, ZeeBest, Watts, Engineered Air, Greenheck, Allen-Bradley
Chiller modules5 × Multistack MS145, R-410A; 680 tons nominal as scheduled
Chiller module electrical575 V, 3 phase, 60 Hz; MCA 149 A, MOP 200 A each
Heat-recovery chillerMultistack MSH165, R-410A; 1,874 MBH heat recovery at design
Heat-recovery chiller nameplate575 V, 3 phase, 60 Hz; MCA 261 A; max breaker 350 A; compressor 42.5 hp, 61.3 A RLA; SCCR 5 kA; 42 lb factory charge
Cooling towerMarley AV6805QAN3 induced-draft crossflow; 10,314 MBH heat rejection at 68 °F wet bulb; 2,118 gal/min, 95 to 85 °F
Tower fansOn variable-frequency drives; 575 V, 3 phase, 60 Hz
Tower tankZeeBest ST-1550, 1,550 Imperial gallons
Chiller pumps3 × Armstrong 4300 6×6×10, 15 hp
Chiller glycol pumps3 × Armstrong 4300 5×5×11½, 30 hp
Condenser-water pumps3 × Armstrong 4300 6×6×11½, 40 hp; 1,059 gal/min at 88 ft
Heat-recovery pumps2 × Armstrong 4380, 5 hp
Heating pumps2 × Armstrong 4300 2×2×6, 7.5 hp
Boiler pumps2 × Armstrong 4380 2×2×6, 2 hp
Pump electrical575 V, 3 phase, 60 Hz; the domestic hot-water circulator is 120 V, 1 phase
Buffer tanksTaco BT3000F 125N, 3,000 gal, ASME (chilled); Taco BT2000F 125N, 2,000 gal (heating)
Make-up air unitEngineered Air FWX73/DJS40/O; gas-fired, 91 MBH; 3,000 CFM at 1 in. ESP; MERV 8 pre-filter and MERV 15 final filter
Roof exhaust fans2 × Greenheck USF-12: 1,500 CFM at 2.0 in. ESP and 1,700 CFM at 2.5 in. ESP
Basis of valuesDesign schedule and nameplates; not a field test

Condition

Used, with about nine months in service. Drained and dry. The equipment is skidded and shrink-wrapped, ready to load. The photos show the plant as it was installed. It is sold as is, where is, as one package. Inspection welcome by appointment; nameplate photos and the equipment schedule are available on request.

Well suited to

  • Hospitals, campuses and large-building owners replacing or adding a central plant
  • Food and beverage plants and other process facilities with year-round cooling and heating loads
  • Controlled-environment growers and greenhouses
  • Arenas and district-energy projects
  • Mechanical contractors who need a matched plant on a short schedule

Load-out and shipping

Rig Out dismantles, crates and loads. Export packing and sea cans are available, with FOB Port of Vancouver or Edmonton rail on request. Freight is quoted per lot and is for the buyer's account.

Email us

Ask a question

We reply within one business day. Prices are in Canadian dollars. Sold as is, where is; see the terms of sale. We use your details only to reply and deal with your enquiry; see our privacy notice.